Natural Ventilation

Location = Libraries/Controls and Performance Data/Natural Ventilation

Type and Sub Type Mapping

The  Type and Sub Type options that can be selected from the drop down lists in that area of the workspace, which filter the Source Library to display the variables the user can select to include, along with a value, in a Library Entry.

 

Type Options Sub Type Options EnergyPlus Objects (IO Reference links)

Air Flow Network

default AirFlowNetwork:SimulationControl

Zone

default AirFlowNetwork:Multizone:Zone

ZoneController

occupant ventilation  

Surface Crack

default AirFlowNetwork:Multizone:Surface:Crack
AirFlowNetwork:Multizone:Surface:ReferenceCrackConditions

 

Air Flow Network (Type)

Default (Sub type)

 

AirflowNetwork Control

The following selections are available to control the Airflow Network simulation:

Note: A ZoneInfiltration:* object indicates any one of ZoneInfiltration:DesignFlowRate, ZoneInfiltration:EffectiveLeakageArea,and ZoneInfiltration:FlowCoefficient objects. A object of ZoneVentilation:* indicates any one of ZoneVentilation:DesignFlowRate and ZoneVentilation:WindandStackOpenArea objects.

Wind Pressure Coefficient Type

Determines whether the wind pressure coefficients are input by the user or calculated. The choices are Input or SurfaceAverageCalculation, with the default being SurfaceAverageCalculation.

AirflowNetwork Wind Pressure Coefficient Array Name

This is the name of the AirflowNetwork:MultiZone:WindPressureCoefficientArray object that contains wind directions corresponding to the wind pressure coefficients given in the AirflowNetwork:MultiZone:WindPressureCoefficientValues objects.

Height Selection for Local Wind Speed Calculation

Determines whether the local wind speed is calculated based on either given external node heights or surface opening heights. The choices are ExternalNode or OpeningHeight, with the default being OpeningHeight. The local outdoor wind speed calculation procedure is given in the section of “Local Wind Speed Calculation” in the Engineering Reference. The calculation procedure requires the height input.

If Wind Pressure Coefficient Type = SurfaceAverageCalculation, a value in this field is not required and a blank may be entered. The default choice is used internally to generate the AirflowNetwork:MultiZone:ExternalNode objects

Building Type

Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The choices for Building Type are LowRise and HighRise, with the default being LowRise.

LowRise corresponds to a rectangular building whose height is less than three times the width of the footprint (wshort in Figure 80) and is less than three times the length of the footprint (wlong in the same figure).

HighRise corresponds to a rectangular building whose height is more than three times the width of the footprint (wshort in Figure 80) or is more than three times the length of the footprint (wlong in the same figure).

Maximum Number of Iterations

The maximum number of iterations allowed in finding an AirflowNetwork solution. If the number of iterations at each simulation timestep is above the maximum number of iterations defined by this field, the program could not find the solution and a Severe error is issued and the program is aborted. The default value is 500.

Initialization Type

Designates which method is used for AirflowNetwork initialization. The choices for Initialization Type are LinearInitializationMethod and ZeroNodePressures, with the default being ZeroNodePressures.

Relative Airflow Convergence Tolerance

The solution is assumed to have converged when is less than the value specified for this input field. This convergence criteria is equivalent to the ratio of the absolute value of the sum of all network airflows ( ) to the sum of network airflow magnitudes ( ). The default value is 1.0x10-4.

Absolute Airflow Convergence Tolerance

The solution is assumed to have converged when the summation of the absolute value of all network airflows ( ) is less than the value specified for this input field. The default value is 1.0x10-6.

Convergence Acceleration Limit

If the ratio of successive pressure corrections is less than this limit, use Steffensen acceleration algorithm (Ref. AirflowNetwork Model in the EnergyPlus Engineering Reference). The range for this field is -1 to 1, with the default value being -0.5.

 

Height Dependence of External Node Temperature

 

Azimuth Angle of Long Axis of Building

Gives the orientation of a rectangular building for calculating wind pressure coefficients. This is the smaller of the angles, measured clockwise, between North and the long axis of the building (see Figure 80). Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The range for this input is 0 to 180, with the default value being 0.

Ratio of Building Width Along Short Axis to Width Along Long Axis

This is the aspect ratio of a rectangular footprint. It is given by the width of the footprint along its short axis divided by the width along the long axis (see Figure 80). If the footprint is square, the value of this field is 1.0. Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation. The range for this input is > 0 to 1, with the default value being 1.

Source: EnergyPlus IO Reference - Footprint of a rectangular building showing variables used by the program to calculate surface-average wind pressure coefficients. The angle a is the “Azimuth Angle of Long Axis of Building.”  wshort/wlong is the “Ratio of Building Width Along Short Axis to Width Along Long Axis.”

 

Zone (Type)

Default (Sub type)

 

 

This object allows control of natural ventilation through exterior and interior openings in a zone, where “opening” is defined as an openable window or door, and it is required to perform Airflow Network calculations.

Ventilation Control Mode

Specifies the type of zone-level natural ventilation control.

Let Tout equal the outdoor air temperature, Tzone equal the previous timestep’s zone air temperature, Tset equal the Vent Temperature Schedule value, Hzone equal the specific enthalpy of zone air from the previous timestep, and Hout equal the specific enthalpy of outdoor air. Then the four allowed choices for Ventilation Control Mode are:

Ventilation Control Zone Temperature Setpoint Schedule Name

The name of a schedule of zone air temperature set points that controls the opening of windows and doors in the thermal zone to provide natural ventilation. This setpoint is the temperature above which all the openable windows and doors in the zone will be opened if the conditions described in the previous field Ventilation Control Mode are met.  The Ventilation Control Zone Temperature Setpoint Schedule Name applies only to windows and doors in the zone that are specified.

Minimum Venting Open Factor

See Figure 1 or Figure 2. This field applies only if Ventilation Control Mode = Temperature or Enthalpy. This value may be from zero to 1.0, with the default being 0.0.

Indoor and Outdoor Temperature Difference Lower Limit For Maximum Venting Open Factor

See Figure 1. This field applies only if Ventilation Control Mode = Temperature. This value may be from zero to less than 100˚C, with the default being 0˚C. The value for this field must be less than the value specified for the following field.

Indoor and Outdoor Temperature Difference Upper Limit for Minimun Venting Open Factor

See Figure 1. This field applies only if Ventilation Control Mode = Temperature. This value must be greater than 0˚C, with the default being 100˚C. The value for this field must be greater than the value specified for the previous field..

Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum Venting Open Factor

See Figure 2. This field applies only if Ventilation Control Mode = Enthalpy. This value may be from zero to less than 300,000 J/kg, with the default being 0 J/kg. The value for this field must be less than the value specified for the following field.

Indoor and Outdoor Enthalpy Difference Upper Limit for Minimun Venting Open Factor

See Figure 2. This field applies only if Ventilation Control Mode = Enthalpy. This value must be greater than zero, with the default being 300,000 J/kg. The value for this field must be greater than the value specified for the previous field.

Figure 1: Modulation of venting area according to inside-outside temperature difference (Source: EnergyPlus IO Reference, Figure 81)

Figure 2: Modulation of venting area according to inside-outside enthalpy difference  (Source: EnergyPlus IO Reference, Figure 82)

 

Note: In order to establish an airflow network, there must be at least two surfaces defined, so that air can flow from one zone into other zones (or to outdoors) through the network (air mass flow conserved).

Venting Availability Schedule Name

The name of a schedule that specifies when venting is available. A zero or negative schedule value means venting is not allowed. A value greater than zero means venting can occur if other venting control conditions are satisfied.

Tip:  If a Venting Availability Schedule Name is not specified, it is assumed that venting is always available.

 

Using Venting Availability Schedule allows you to turn off venting at certain times of the day (at night, for example), of the week (on weekends, for example), or of the year (during the winter, for example).

 

If used with Ventilation Control Mode = Constant, the ventilation rate is constant only when this schedule allows venting; otherwise the ventilation rate is set to zero.

If Ventilation Control Mode = NoVent, this schedule has no effect.

 

Single Sided Wind Pressure Coefficient Algorithm

Facade Width

Occupant Ventilation Control Name

 

Zone Controller (Type)

Occupant Ventilation (Sub Type)

 

Minimum Opening Time

Minimum Closing Time

Thermal Comfort Low Temperature Curve Name

Thermal Comfort Temperature Boundary Point

Thermal Comfort High Temperature Curve Name

Maximum Threshold for Persons Dissatisfied PPD

Occupancy Check

Opening Probability Schedule Name

Closing Probability Schedule Name

 

Surface Crack (Type)

Default (Sub type)

 

 

Specifies the properties of air flow through a crack and the associated measurement conditions. The following power law form is used that gives air flow through the crack as a function of the pressure difference across the crack:

 

Where

Q   = air mass flow (kg/s)

CQ  = air mass flow coefficient (kg/s-Pan @ 1 Pa)

CT  = reference condition temperature correction factor (dimensionless)

= pressure difference across crack (Pa)

n    = air flow exponent (dimensionless)

 

where

ρ = Air density at the specific air temperature and humidity ratio conditions [kg/m3]

ν = Air kinetic viscosity at the specific air temperature condition [m2/s]

ρo = Air density at the reference air conditions provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [kg/m3]

νo = Air kinetic viscosity at the reference air temperature provided by the object AirflowNetwork:MultiZone:ReferenceCrackConditions specified in the field Reference Crack Conditions [m2/s]

AirFlowNetwork:Multizone:Surface:Crack

Air Mass Flow Coefficient at Reference Conditions

The value of the air mass flow coefficient, , in the crack air flow equation. It has units of kg/s at 1Pa. This value must be greater than zero.

Air Mass Flow Exponent

The value of the exponent, n, in the crack air flow equation. The valid range is 0.5 to 1.0, with the default value being 0.65.

AirFlowNetwork:Multizone:Surface:ReferenceCrackConditions

Specifies the reference conditions for temperature, humidity, and pressure..

Reference Temperature

The reference temperature in °C under which the Surface Crack Data were obtained. The default value is 20°C.

Reference Barometric Pressure

The reference barometric pressure in Pa under which the Surface Crack Data were obtained. The default value is 101325 Pa.

Reference Humidity Ratio

The reference humidity ratio in kg/kg under which the Surface Crack Data were obtained. The default value is 0 kg/kg.

 

 

______________________________________________________________________________________

© Copyright 2013 Simergy, Sustainable IQ, Inc.