Stencil: Zone HVAC Stencil: Grp-CV Term w/reheat
Type: Air Terminal
Sub Type: ConstantVolume_Reheat
Note: Requires a connection to a hot water loop
EnergyPlus Object - AirTerminal:SingleDuct:ConstantVolume:Reheat
The AirTerminal:SingleDuct:ConstantVolume:Reheat or terminal reheat system is a constant volume reheat system. The systems cooling capabilities are provided by way of cooling coil that supplies cooling to the entire supply air volume. The cooling coil is controlled by a controller setpoint specified for the cooling coil. Zone control is accomplished by heating (reheating) the airflow into each zone as determined by the zone thermostat. Currently the reheat can be supplied by a electric, gas, or hot water coil that tries to meet the zone demand.
The table shows the properties that are displayed when the component is selected while in diagram mode. The second column shows the selection options available that are dictated by EnergyPlus or it shows the source for the library entries that are displayed in the drop down list.
Property Name | Value Sources/Options |
Name |
Simergy provides unique name (editable) |
Availability Schedule Name |
|
Maximum Air Flow Rate |
0-Min, Autosize |
Reheat Coil Name |
|
Maximum Hot Water or Steam Flow Rate |
0, Autosize |
Minimum Hot Water or Steam Flow Rate |
0-Min; 0 default |
Convergence Tolerance |
0-Min; 0.001 Default |
Maximum Reheat Air Temperature |
32C-Min |
Simergy automatically defines a unique name for each component. This can be changed by the user if desired.
Schedule that this component will operate or is available to operate.
The design constant volume flow rate (m3/sec) specified for the terminal reheat ADU.
Reheat Coil Object name being simulated with this ADU. Applicable for all coils.
This field is 0 for gas and electric coils. Set to the maximum design water flow (m3/sec) for the hot water coil
This field is zero for gas and electric coils. Set to the minimum design water flow (m3/sec) for the hot water coil, normally set to be a shut off valve that is set to zero.
The coil is controlled by knowing the zone demand determined by the zone thermostat and setting the outlet conditions to meet this demand. For the electric and gas coils, this is set exactly since the coil model solution can be inverted. With the hot water coil that uses an effectiveness-NTU method, the solution cannot be inverted directly. Therefore, to determine the correct mass flow rate for the hot water the solution is solved for by iteration. The iterative solution uses an interval halving routine and needs a termination criteria that is set with the Convergence Tolerance parameter. This control offset is set to a decimal fraction of the zone demand as the criteria, i.e. 0.001. The default for the field is 0.001.
This is the upper limit on the temperature in degrees C of the air leaving the terminal unit – reheat coil (and being delivered to the zone). If the user leaves this field blank, no maximum reheat air temperature is enforced.
______________________________________________________________________________________
© Copyright 2013 Simergy, Sustainable IQ, Inc.