Simergy's approach to autosizing is the same that is used by EnergyPlus and described in detail in the EnergyPlus Input Output Reference Guide.
The table identifies requirements to successfully do component autosizing (left column) and the location within the Simergy Interface where they are located (right column).
Requirements | Location in Simergy |
Input file should contain a Simulation Control object | Template/Simulation Parameters references a SimSimulationParameters/SimulationControl/Default object. This template is assigned in the simulation workspace to a simulation configuration. |
At least two SizingPeriod objects need to be included | Design Alternatives/Select Design Alternatives -The weather download service automatically downloads all 18 design days and imports them when they are available Tip: Location names without design days are indicated in italics in the Design Alternative workspace. Note: in order to adjust the design days or define new ones, go to the library or template workspace and switch to the Project Model. |
Sizing: Parameters object included if applying global sizing | Template/System Parameters - the Global Sizing object is located in the Input Values table. |
A Sizing:Zone object for each controlled zone that is unique | Systems/ZoneHVACGroups/Create/Edit workspace - A Sizing Object can be assigned to the system via the Sizing Property |
A Sizing: System object for each HVAC Air Loop | Systems/Air Loops/Create/Edit workspace - A Sizing Object can be assigned to the system via the Sizing Property |
A Sizing: Plant object for each Plant or Condenser Loop | Systems/Water Loops/Create/Edit workspace - A Sizing Object can be assigned to the system via the Sizing Property |
A ZoneControl:Thermostat for each conditioned zone (even slave zones) must be included to be recognized as a 'conditioned zone' and included in the simulation | Template/Zone Conditions Template |
Confirm that Summer Design Day and Winter Design Day Schedules are included | Design Alternatives/Select Design Alternatives - The 1 % Cooling (Winter Design Day) and 99% Heating (Summer Design Day) days are assigned to the Location Template by default. Note: In order to adjust The Summer and Winter Design days or to define new ones, the user can go to the Library or Template workspace and switch to the Project Model. |
User must coordinate sizing inputs with actual simulation control inputs | Simergy automatically sets the Simulation Control Sizing to account for the Sizing Object that are assigned to the Loops. For example - If an air loop has a sizing object assigned, the "Do System Sizing Calculation" is automatically set to YES. |
Note: Sizing:System and Sizing:Zone objects determine the supply temperatures for central heating and cooling loads. Other components such as heat recovery, fans, pumps and dehumidifiers are not factored into the sizing calculation.
Within the EnergyPlus Input Output Reference Guide Table 22 - Details of Autosizable Objects/Fields displays a large two column table that identifies the Component/Object and then the Autosizable Fields (Properties) that are associated with the component. A number of the library entries within the Libraries Categories for the content that is packaged with Simergy have these properties set to "Autosize", however it is important to always check. If a field/property can be "autosized", it will have "autosize" available from the drop down list.
The table shows the different places within Simergy where you can define sizing parameters.
Tip: At a basic level you can set sizing factors overall, at the Zone Group level, and at the individual component level for certain components. The thing to remember is that if you define a sizing factor at the Zone Group level it will override the global sizing factor.
Simergy Information |
EnergyPlus Objects + Description |
Libraries > Sizing Params Type = HvacDesign Sub Type = Sizing Related Template = Simulation Parameters |
IDF = Sizing:Parameters You can specify an overall sizing factor, which will be applied to all the Zone Design Loads and Air Flow rates resulting from the zone sizing calculations. |
Libraries > Sizing Params Type = HvacDesign Sub Type = ZoneSizing Related Template = Zone Conditions |
IDF = Sizing:Zone You can specify a sizing factor for a specific Zone Group, which is applied to the calculated zone design loads and air flow rates. This sizing factor overrides the sizing factor described above. |
Libraries > Plant Eqmt Type = Boiler, Chiller, ChillerHeater, and Cooling Tower Sub Type = <all associated with Types> Related Template = Water Loops |
Boiler = Boiler:HotWater Boiler= Boiler:Steam Chiller = Chiller:Electric:EIR Chiller = Chiller:Electric:ReformulatedEIR Chiller= Chiller:Electric Chiller= Chiller:ConstantCOP Chiller= Chiller:EngineDriven Chiller= Chiller:CombustionTurbine Chiller= Chiller:AbsorptionIndirect Chiller= Chiller:Absorption Chiller= ChillerHeater:Absorption:DoubleEffect ChillerHeater= ChillerHeater:Absorption:DirectFired CoolingTower = CoolingTower:SingleSpeed CoolingTower = CoolingTower:TwoSpeed CoolingTower = CoolingTower:VariableSpeed You can specify a sizing factor that modifies the autosized component capacity and flow rates, which is applied after the global and zone group sizing factors. They are used to split the design load between multiple components, and they can change the autosizing of the associated loops and pumps. Rules for how sizing factors of plant components effect loops and pumps:
|
Mixed user-specified and autosized inputs can be successfully used if the following points and suggestions are followed.
Requirements | How Simergy handles it? |
Each component is autosized independently |
The user has total control over which fields are set to autosize. Simergy contains validation rules that evaluate if the loop level sizing object is missing when any component has an autosize value assigned to it. |
For a component it is recommended that all inputs are either autosized or are all user-specified |
|
Sizing: Parameters object included if applying global sizing | |
Sizing information flows from sizing objects to components, so sizing calculations have no knowledge of user-specified values in a component. *Only exception is plant loop sizing that collects all component design water flow rates |
|
If user wants to specify a zone or system air flow rate it should be done using the Sizing:Zone and Sizing:System objects. | |
The plant loop flow rates are sized from the total design demand of the components connected to each loop. The components demanding water need not be autosized for the plant loop autosizing to work successfully. |
The results of the component autosizing calculations to be viewed within Results Visualization the output variables must be included in the Output Request Set. A complete list of Objects with autosized fields is provided below. Source = EnergyPlus Input Output Reference Guide - Table 23.
The results of the component autosizing calculations are also reported in the eplusout.eio file. For each component field that has been autosized the component, component name, field description, and value are displayed as comma separated data on a line beginning with Component Sizing. For examples see the EnergyPlus Output Details and Examples document.
Object Name |
Object Name |
AirConditioner:VariableRefrigerantFlow |
AirLoopHVAC |
AirLoopHVAC:Unitary:Furnace:HeatCool |
AirLoopHVAC:Unitary:Furnace:HeatOnly |
AirLoopHVAC:UnitaryHeatCool |
AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass |
AirLoopHVAC:UnitaryHeatOnly |
AirLoopHVAC:UnitaryHeatPump:AirToAir |
AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed |
AirLoopHVAC:UnitaryHeatPump:WaterToAir |
AirTerminal:DualDuct:ConstantVolume |
AirTerminal:DualDuct:VAV |
AirTerminal:DualDuct:VAV:OutdoorAir |
AirTerminal:SingleDuct:ConstantVolume:CooledBeam |
AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction |
AirTerminal:SingleDuct:ConstantVolume:Reheat |
AirTerminal:SingleDuct:ParallelPIU:Reheat |
AirTerminal:SingleDuct:SeriesPIU:Reheat |
AirTerminal:SingleDuct:Uncontrolled |
AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat |
AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat |
AirTerminal:SingleDuct:VAV:NoReheat |
AirTerminal:SingleDuct:VAV:Reheat |
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan |
Boiler:HotWater |
Boiler:Steam |
Branch |
Chiller:Absorption |
Chiller:Absorption:Indirect |
Chiller:CombustionTurbine |
Chiller:ConstantCOP |
Chiller:Electric |
Chiller:Electric:EIR |
Chiller:Electric:ReformulatedEIR |
Chiller:EngineDriven |
ChillerHeater:Absorption:DirectFired |
ChillerHeater:Absorption:DoubleEffect |
Coil:Cooling:DX:MultiSpeed |
Coil:Cooling:DX:SingleSpeed |
Coil:Cooling:DX:TwoSpeed |
Coil:Cooling:DX:VariableRefrigerantFlow |
Coil:Cooling:Water |
Coil:Cooling:Water:DetailedGeometry |
Coil:Cooling:WaterToAirHeatPump:EquationFit |
Coil:Cooling:WaterToAirHeatPump:ParameterEstimation |
Coil:Heating:DX:MultiSpeed |
Coil:Heating:DX:SingleSpeed |
Coil:Heating:DX:VariableRefrigerantFlow |
Coil:Heating:Electric |
Coil:Heating:Gas |
Coil:Heating:Steam |
Coil:Heating:Water |
Coil:Heating:WaterToAirHeatPump:EquationFit |
Coil:Heating:WaterToAirHeatPump:ParameterEstimation |
CoilPerformance:DX:Cooling |
CondenserLoop |
Controller:OutdoorAir |
Controller:WaterCoil |
CoolingTower:SingleSpeed |
CoolingTower:TwoSpeed |
CoolingTower:VariableSpeed |
EvaporativeCooler:Indirect:ResearchSpecial |
EvaporativeFluidCooler:SingleSpeed |
EvaporativeFluidCooler:TwoSpeed |
Fan:ComponentModel |
Fan:ConstantVolume |
Fan:OnOff |
FanPerformance:NightVentilation |
Fan:VariableVolume |
FluidCooler:SingleSpeed |
FluidCooler:TwoSpeed |
HeaderedPumps:ConstantSpeed |
HeaderedPumps:VariableSpeed |
HeatExchanger:AirToAir:SensibleAndLatent |
HeatExchanger:WatersideEconomizer |
HVACTemplate:Plant:Boiler |
HVACTemplate:Plant:Chiller |
HVACTemplate:Plant:Tower |
HVACTemplate:System:DedicatedOutdoorAir |
HVACTemplate:System:PackagedVAV |
HVACTemplate:System:Unitary |
HVACTemplate:System:UnitaryHeatPump:AirToAir |
HVACTemplate:System:VAV |
HVACTemplate:Zone:FanCoil |
HVACTemplate:Zone:PTAC |
HVACTemplate:Zone:PTHP |
HVACTemplate:Zone:Unitary |
HVACTemplate:Zone:VAV |
HVACTemplate:Zone:VAV:FanPowered |
HVACTemplate:Zone:WaterToAirHeatPump |
PlantEquipmentOperation:ComponentSetpoint |
PlantLoop |
Pump:ConstantSpeed |
Pump:VariableSpeed |
Pump:VariableSpeed:Condensate |
Sizing:System |
SolarCollector:FlatPlate:PhotovoltaicThermal |
ThermalStorage:ChilledWater:Mixed |
ThermalStorage:ChilledWater:Stratified |
WaterHeater:Mixed |
WaterHeater:Stratified |
ZoneHVAC:Baseboard:Convective:Electric |
ZoneHVAC:Baseboard:Convective:Water |
ZoneHVAC:Baseboard:RadiantConvective:Electric |
ZoneHVAC:Baseboard:RadiantConvective:Steam |
ZoneHVAC:Baseboard:RadiantConvective:Water |
ZoneHVAC:EnergyRecoveryVentilator |
ZoneHVAC:FourPipeFanCoil |
ZoneHVAC:HighTemperatureRadiant |
ZoneHVAC:IdealLoadsAirSystem |
ZoneHVAC:LowTemperatureRadiant:Electric |
ZoneHVAC:LowTemperatureRadiant:VariableFlow |
ZoneHVAC:OutdoorAirUnit |
ZoneHVAC:PackagedTerminalAirConditioner |
ZoneHVAC:PackagedTerminalHeatPump |
ZoneHVAC:TerminalUnit:VariableRefrigerantFlow |
ZoneHVAC:UnitHeater |
ZoneHVAC:UnitVentilator |
ZoneHVAC:VentilatedSlab |
ZoneHVAC:WaterToAirHeatPump |
ZoneHVAC:WindowAirConditioner |
|
______________________________________________________________________________________
© Copyright 2013 Simergy, Sustainable IQ, Inc.